Fire resistant Cable as AS3013

CU/MT/X-HF-110/HFS-110-TP 0.6/1kV Multicore cable as AS/NZS3013
Multicore X-HF-110 insulated HFS-110-TP sheathed fire resistant cable

Application: Fire Resistant - Mains and Sub-Mains, Fire Alarm Systems, Essential Services

 

Construction:

1.    Conductor - Plain annealed class 5 flexible copper

2.    Fire Resistant layer - Mica Tape

3.    Insulation – Cross-linked low-smoke halogen-free polyolefin compound (X-HF-110)

4.    Filler - Flame retardant material

5.    Binder Tape - Low smoke halogen-free flame retardant tape

6.    Outer sheath - Cross-linked low-smoke halogen-free polyolefin compound (HFS-110-TP)

 

Cross Section

2 core: 1.5~400mm2

3 core: 1.5~400mm2

4 core: 1.5~400mm2

5 core: 1.5~400mm2

2 core + earth: 1.5~400mm2

3 core + earth: 1.5~400mm2

4 core + earth: 1.5~400mm2

 

Temperature characteristics:                    

Conductor operating temperature: -40~110                

Min. temperatrue laying condition: 0                 

 

Electrical Characteristics:

Rated voltage: 0.6/1 (1.2) kV

High voltage test: 3.5kV / 5min

 

Color:

Insulation:

2 core: Red, Black

3 core: Red, White, Blue
4 core: Red, White, Blue, Black 

5 core: Red, White, Blue, Black, Y/G

2 core + earth: Red, Black, Y/G

3 core + earth: Red, White, Blue, Y/G

4 core + earth: Red, White, Blue, Black, Y/G


Sheath: Red or according to customer requirements

 

Standard:

Cable design: AS/NZS5000.1

Conductor: AS/NZS 1125

Fire resistant : AS/NZS3013 (WS52W)

Low Voltage Power Cable

Contact us for more information about our products.